We're hiring automation, industrial AI and test engineers.

Apply now
VarinAutomation
3D view of the PPT-1 boards inside the see-through DIN housing

Position measurement

PPT-1 Position Transmitter

Reads a potentiometer on 28 V DC or 400 Hz AC and shows its position in %, mm or degrees, on the panel and over Modbus RTU.

Delivery in 4 weeksModel PPT-1
Input
3-wire potentiometer
Excitation
10–51 V peak, DC or AC
Display units
%, mm or degrees
Interface
Isolated RS-485 Modbus RTU
Supply
12–30 V DC, about 1 W
Housing
DIN 144 × 72 mm panel mount
Price on requestAdd to your basket for a formal quotation.

Delivery within 4 weeks of order · anywhere in India

Ask on WhatsApp

Overview

Read a potentiometer's position without loading its circuit.

The PPT-1 reads the position of a potentiometer that is already powered by 28 V DC or 28 V AC (400 Hz typical) and shows it on a panel display and over Modbus RTU. It samples the wiper and the excitation at the same instant, so the reading is a true ratio and does not move when the excitation voltage changes.

Each input is over 5 MΩ, so the PPT-1 can sit alongside an existing indicator or controller without loading the sensor. It accepts ±50 V between the pot circuit and its own ground, and 90 V gas discharge tubes to PE protect the input from surges on field wiring.

Choose %, mm or degrees, set zero and full scale with the CAL key, and read position, excitation and fault status from a Delta (or any Modbus RTU master) HMI over isolated RS-485. It fits a standard 144 × 72 mm DIN panel cut-out.

PPT-1 OLED main screen showing 47.2 % position with 28.1 V AC excitation at 400 Hz
Front-panel display: 47.2 %, 400 Hz AC excitation at 28.1 V
DC or AC excitation
10–51 V
Input impedance
> 5 MΩ
Position updates
10 / s
RS-485 Modbus RTU
Isolated

Why engineers choose the PPT-1

  • Ratiometric readingWiper and excitation sampled together by a 24-bit ADC, so supply swings don't shift the position.
  • DC or AC excitation10–51 V peak, DC or AC from about 25 Hz to 1 kHz, including 28 V DC and 28 V AC 400 Hz.
  • Doesn't load the sensorOver 5 MΩ per input, ±50 V common-mode range and 90 V gas discharge tubes to PE.
  • Clear front panel1.3" OLED with position, bar graph, excitation type, frequency, voltage and status.
  • Two-step calibrationMove to zero, press; move to full scale, press. Stored in EEPROM, from the panel or over Modbus.
  • Fault detectionFlags lost excitation, an open or out-of-range wiper and over-range, with a red FAULT lamp.
  • Isolated Modbus RTURS-485 at 9600, 19200 or 38400 baud with function codes 03, 04, 06 and 16.
  • Quick wiringPluggable 5.08 mm terminals on the rear for power, sensor and RS-485.
Used for
  • Potentiometric position sensors
  • Valve & actuator position feedback
  • 28 V DC and 400 Hz AC systems
  • Linear & rotary pot readout
  • HMI & SCADA position monitoring
  • Test benches

Specifications

Technical data

Sensor input
Sensor3-wire potentiometer: excitation +, excitation −, wiper, plus shield / PE
Excitation (from the sensor circuit)10–51 V peak, DC or AC, e.g. 28 V DC or 28 V AC 400 Hz
AC frequencyAbout 25 Hz to 1 kHz
Input impedanceEXC+ 6.14 MΩ, EXC− 6.14 MΩ, wiper 5.78 MΩ (DC and 400 Hz)
Common-mode range±50 V between the pot circuit and the transmitter ground
Surge protection90 V gas discharge tubes to chassis / PE
MethodRatiometric: wiper and excitation sampled together by a 2-channel 24-bit ADC
Measurement
Position0–100 % (0.01 % over Modbus), or mm / degrees with a user-set span
Update rate10 results per second
Filter0.1, 0.5, 1 or 2 s
Calibration2-point zero and span, from the panel or over Modbus, stored in EEPROM
Also measuredExcitation voltage (RMS for AC), frequency and supply voltage
Fault detectionNo excitation (< 10 V), wiper fault (open or ratio outside 0.02–0.98), over-range
Communication
InterfaceRS-485, 2-wire, galvanically isolated
ProtocolModbus RTU slave; function codes 03, 04, 06, 16
Address1–247 (default 1)
Baud rate9600, 19200, 38400 (default 9600)
Framing8N1
Bus termination120 Ω, jumper selectable
Front panel
Display1.3" 128 × 64 OLED
ControlsRotary encoder with push, CAL key, MENU key
IndicatorRed FAULT lamp
Main screenPosition and bar graph, excitation type, frequency and voltage, status
Power & mechanical
Supply12–30 V DC, about 1 W
Supply protectionResettable fuse, reverse-polarity diode and surge clamp
HousingDIN 144 × 72 mm (IEC 61554) panel instrument case
Panel cut-out138 (+1.0) × 68 (+0.7) mm
MountingPanel clamps from behind
Field terminalsPluggable 5.08 mm blocks on the rear: power, sensor, RS-485
Firmwarev1.0, field-updatable over ISP

Wiring

Rear terminals

Pluggable 5.08 mm blocks on the rear. Connect the PPT-1 across the existing pot: its high-impedance inputs read the excitation already on the circuit and do not supply it. Bond terminal 4 to PE so the surge protection has a path to earth.

RS-485

Modbus RTU (isolated)

  1. ARS-485 A
  2. BRS-485 B
  3. GNDIsolated signal ground

SENSOR

Potentiometer input

  1. 1Excitation +
  2. 2Excitation −
  3. 3Wiper
  4. 4Shield / PE

POWER

12–30 V DC

  1. +VSupply +
  2. 0 VSupply 0 V

Ordering

Codes and what's included

Ordering
PPT-1Potentiometer Position Transmitter, DC or AC excitation, front panel + isolated RS-485 Modbus RTU
In the box
PPT-1 in DIN 144 × 72 mm housing with panel clamps
Mating pluggable terminal plugs for power, sensor and RS-485
Wiring and Modbus register guide

Modbus RTU

Register map

1-based addressing: 30001 and 40001 are protocol address 0. Floats use two registers, high word first.

AddressRegisterAccessMeaning
30001POSITIONRPosition in 0.01 %
30002–30003POSITION_UNITSRPosition in the chosen units (float)
30004RATIORWiper ratio × 10000
30005EXC_VOLTSRExcitation in V × 100 (RMS for AC)
30006EXC_FREQRExcitation frequency in Hz × 10 (0 = DC)
30007STATUSRBits: no excitation, wiper fault, over-range, not calibrated
30008SUPPLYRSupply in V × 100
40001ADDRESSR/WSlave address 1–247
40002BAUDR/W0 = 9600, 1 = 19200, 2 = 38400
40003UNITSR/W0 = %, 1 = mm, 2 = degrees
40004–40005SPANR/WFull-scale value in mm or degrees (float)
40006FILTERR/W0 = 0.1 s, 1 = 0.5 s, 2 = 1 s, 3 = 2 s
40007COMMANDW1 = capture zero, 2 = capture span, 3 = factory reset
40008–40011CAL_ZERO / CAL_SPANR/WCalibrated ratios at zero and full scale (floats)

Need it in your panel or test bench?

Add it to your basket and request a quotation, or talk to us about HMI screens and integration.