We're hiring automation, industrial AI and test engineers.

Apply now
VarinAutomation
3D view of the MVS-100 boards inside the see-through DIN housing

Calibration & test

MVS-100 Precision mV Source

±100 mV in 0.01 mV steps, set from the front panel or an HMI over Modbus RTU.

Made to orderModel MVS-100
Output
−100.00 … +100.00 mV DC
Resolution
0.01 mV
Load current
±20 mA, source and sink
Interface
Isolated RS-485 Modbus RTU
Supply
12–24 V DC, 3 W max
Housing
DIN 144 × 72 mm panel mount
Price on requestBuilt and calibrated to order. Add to your basket for a formal quotation.
Ask on WhatsApp

Overview

A dependable millivolt reference for your panel or bench.

The MVS-100 generates a stable DC millivolt signal from −100.00 to +100.00 mV for checking and calibrating thermocouple inputs, load-cell and strain-gauge amplifiers, transmitters and DAQ channels. It fits a standard 144 × 72 mm DIN panel cut-out, so a test bench or panel door gets a permanent, repeatable reference.

Set the output from the front panel with the knob, or hand control to a Delta (or any Modbus RTU master) HMI over isolated RS-485. Only one place controls the output at a time, and the display always shows which: REM, LOC or LCK.

A 4-wire Kelvin output with remote sense corrects cable drop at the load, and the output stage sources and sinks up to 20 mA. If the HMI link is lost, a configurable timeout drops the output to 0 mV.

MVS-100 OLED main screen showing output ON at +45.27 mV in LOCAL mode
Front-panel display: output ON at +45.27 mV, 0.01 mV step
Output range
±100 mV
Setting steps
0.01 mV
Source and sink
±20 mA
RS-485 Modbus RTU
Isolated

Why engineers choose the MVS-100

  • Fine, stable output−100.00 to +100.00 mV DC in 0.01 mV steps, from a 3.18 µV hardware resolution.
  • Sources and sinks 20 mA4-wire FORCE / SENSE output corrects cable drop right at the load.
  • Isolated Modbus RTURS-485 at 9600–115200 baud with function codes 03, 04, 06 and 16.
  • Clear front panel1.3" OLED, rotary knob, OUTPUT and MENU keys, and an output-ON lamp.
  • Remote or local controlOne place controls the output at a time; the HMI can lock the front panel.
  • Guided calibration2-point calibration from the panel or over Modbus, stored in EEPROM.
  • Fails safeComm-loss timeout drops the output to 0 mV, and OFF holds a calibrated 0.00 mV.
  • Quick wiringPluggable 5.08 mm terminals on the rear for power, output and RS-485.
Used for
  • Thermocouple input checks
  • Strain-gauge & load-cell amplifiers
  • Transmitter calibration
  • DAQ & PLC analog input testing
  • Automated test equipment (ATE)
  • Panel-mounted reference source

Specifications

Technical data

Output
Range−100.00 to +100.00 mV DC
Setting resolution0.01 mV (3.18 µV hardware resolution)
Load current±20 mA, sources and sinks (current limit ≈ 28 mA)
Connection4-wire: FORCE+, SENSE+, SENSE−, FORCE− / GND
Verified accuracy after calibration±0.01 mV at +100, 0 and −100 mV
Settling≈ 1.6 ms to 1 µV after a 10 mV step
Output OFF / comm lossActively held at 0.00 mV (calibrated)
Communication
InterfaceRS-485, 2-wire, galvanically isolated
ProtocolModbus RTU slave; function codes 03, 04, 06, 16; broadcast writes
Address1–247 (default 1)
Baud rate9600, 19200, 38400, 57600, 115200 (default 9600)
Framing8 data bits, parity None / Even / Odd, 1 stop (default 8N1)
Bus termination120 Ω, jumper selectable
Comm timeoutSet in seconds (0 = off); output drops to 0 mV on timeout
Front panel
Display1.3" 128 × 64 OLED, adjustable brightness and auto-dim
ControlsRotary encoder with push, OUTPUT key, MENU key
IndicatorOutput-ON lamp (light pipe)
ModesREMOTE (Modbus), LOCAL (panel), LCK (panel locked by HMI)
CalibrationGuided 2-point (−30 / +30 mV) with DMM entry
Power & mechanical
Supply12–24 V DC, 3 W max
HousingDIN 144 × 72 mm (IEC 61554) panel instrument case
Panel cut-out138 (+1.0) × 68 (+0.7) mm
Depth behind panel124 mm
MountingPanel clamps from behind
Field terminalsPluggable 5.08 mm blocks on the rear: power, output, RS-485
Firmwarev3.1, field-updatable over ISP

Wiring

Rear terminals

Pluggable 5.08 mm blocks, left to right as seen from the rear. For loads near 20 mA, run the SENSE wires to the load to cancel cable drop. Output 0 V is common with the supply 0 V, so use an isolated supply.

RS-485

Modbus RTU (isolated)

  1. D+RS-485 A
  2. D−RS-485 B
  3. SGIsolated signal ground

OUTPUT

±100 mV output

  1. F+FORCE+
  2. S+SENSE+
  3. S−SENSE−
  4. F−FORCE− / GND

POWER

12–24 V DC

  1. +VSupply +
  2. 0 VSupply 0 V

Ordering

Codes and what's included

Ordering
MVS-100Precision mV Source, ±100 mV, front panel + isolated RS-485 Modbus RTU
Option: HMI screensReady-made Delta DOPSoft / DIAScreen screens for setpoint, ON/OFF and calibration
Option: calibration reportMulti-point verification against a 6½-digit DMM
In the box
MVS-100 in DIN 144 × 72 mm housing with panel clamps
Mating pluggable terminal plugs for power, output and RS-485
Factory calibration values, stored in the unit
Wiring, HMI setup and Modbus register guide

Modbus RTU

Register map

Holding registers, 16-bit word, 1-based 4x addressing. Read 40007 = 769 (firmware v3.1) to confirm your HMI's address offset.

AddressRegisterAccessMeaning
40001SETPOINTR/WOutput in 0.01 mV, signed: −10000 … +10000
40002OUTPUT_ENR/W0 = held at 0 mV, 1 = output on
40004STATUSROutput on, clamped, calibrated, comm timeout, LOCAL mode bits
40005 / 40006CAL_OFFSET / CAL_GAINR/WCalibration offset (0.1 µV) and gain (ppm)
40007FW_VERSIONR769 = v3.1
40008–40010SLAVE_ID / BAUD / PARITYR/WCommunication settings (apply after save)
40011–40013CAL_CMD / CAL_MEAS_LO / HIR/W2-point calibration over Modbus
40014COMM_TIMEOUTR/WSeconds, 0 = off
40015POWERUP_MODER/W0 = start at 0 mV off, 1 = restore setpoint
40016FP_LOCKR/W1 = front panel locked by the HMI
40017MODER/W0 = LOCAL, 1 = REMOTE

Need it in your panel or test bench?

Add it to your basket and request a quotation, or talk to us about HMI screens and integration.